APPENDICES
(31)CH Difference conversion trigger (Un\G172 to Un\G175)
Use this buffer memory area as a trigger to start or stop the difference conversion for each channel.
For details on the difference conversion function, refer to the following.
• Difference Conversion Function (
Page 126, Section 8.12)
Difference conversion trigger
Setting value
No request
0
Trigger request
1
A
(a) Starting/Stopping the difference conversion
• When the setting value is turned from No request (0) to Trigger request (1), the difference conversion
starts.
• When the setting value is turned from Trigger request (1) to No request (0), the difference conversion
stops.
(b) Default value
The default value is No request (0). (All channels)
A channel where a value other than the above values is set brings about an error. Error code (37) is stored in Latest error
code (Un\G19), Error flag (XF) turns on, then the ERR. LED turns on. The difference conversion continues.
(32)CH Difference conversion reference value (Un\G180 to Un\G183)
This area stores the digital operation value at the start of the difference conversion as the difference conversion
Appendix 2 Details of Buffer Memory Addresses
reference value.
For details on the difference conversion function, refer to the following.
• Difference Conversion Function (
Page 126, Section 8.12)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Data section
Sign bit
1: Negative
0: Positive
(a) Setting range
The setting range is between -32768 and 32767.
● The difference conversion reference value is updated when CH Difference conversion trigger (Un\G172 to Un\G175) is
turned from No request (0) to Trigger request (1).
● Even if CH Difference conversion status flag (Un\G190 to Un\G193) is turned from Converting difference (1) to Not
converted (0), CH Difference conversion reference value (Un\G180 to Un\G183) is not cleared.
259