Download Manual - Festo
Transcript
6. Diagnosis and fault display 6.4 Diagnostic memory The diagnostic memory contains the last 16 diagnostic messages. It is backed up if possible in the event of power failure. If the memory is full, the oldest element will be overwritten (ring buffer). Structure of the diagnostic memory Parameters 1) PNU 200 (20C8h) PNU 201 (20C9h) PNU 202 (20CAh) PNU 203 (20CBh) Format uint8 uint16 uint32 uint32 Meaning Diagnostic event Fault number Time stamp Cycle number Subindex 1 Current diagnostic message Subindex 2 Previous diagnostic message ... ... Subindex 16 1) Oldest diagnostic message See section B.3.5 Tab.6/8: Diagnostic memory: structure Configuration of diagnostic memory with PNU 204/(20CCh) SI Description Specifi cation Min Max 1 = 1: Record incoming and outgoing *) faults = 2: Record only incoming faults 1 1 2 *) Outgoing fault = Acknowledge the fault 2 = 1: Resolution time stamp 10 ms = 2: Resolution time stamp 1 ms 1 1 2 3 Deleting the diagnostic memory Writing with value = 1 deletes the diagnostic memory Read will always reply with value = 1 0 0 1 4 Read the number of entries in the diagnostic memory 0 0 16 Tab.6/9: Diagnostic memory: configuration Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH 6−13