Connection of external controls (VD2/VD2A only)
(continued)
Modulating boilers – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and
the other settings are dependent on the
safety equipment installed in
accordance with applicable codes.
Non-condensing boiler
(VD2/VD2A) °C / °F
Condensing boiler
(CT3) °C / °F
Condensing boiler
(CM2) °C / °F
Fixed high limit
110 / 230
99 / 210
99 / 210
99 / 210
Adjustable high limit
100 / 212
95 / 203
95 / 203
95 / 203
93 / 200
87 / 188
87 / 188
88 / 190
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
Single-boiler systems:
Coding ”01: 1”
(factory setting)
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is
connected, only the connections on
plug aVD are required. The DHW tank
control unit is activated when the DHW
tank temperature sensor is connected.
The boiler water temperature must be
set to the minimum value.
When a building automation
system is connected, the
connections on plugs aVD and
aVH are required.
The DHW tank temperature and
the load-dependent cascade control
must be controlled through the
external building automation
system.
CAUTION
5285 941 v.1.5
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler
MUST be constantly closed.