Table 8 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
F. NORMAL RUN
PRIMARY MESSAGE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
SECONDARY MESSAGE
4-20 mA SIGNAL
REMOTE TEMP SENSOR
CHW TEMP DIFFERENCE
LEAVING CHILLED WATER
ENTERING CHILLED WATER
TEMPERATURE RAMP LOADING
BY DEMAND RAMP LOADING
BY LOCAL DEMAND SETPOINT
BY 4-20 mA SIGNAL
BY CCN SIGNAL
BY LOADSHED/REDLINE
HOT GAS BYPASS
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
BY LOCAL SIGNAL
ICE BUILD MODE
CAUSE/REMEDY
Auto chilled water reset active based on external input.
Auto chilled water reset active based on external input.
Auto chilled water reset active based on cooler D T.
Default method of temperature control.
Entering Chilled Water (ECW) control enabled in TEMP_CTL screen.
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Demand limit set point is less than actual demand.
Demand limit is active based on external auto demand limit option.
Demand limit is active based on control limit signal from CCN.
Demand limit is active based on LOADSHED screen set-up.
Hot gas bypass option is energized. See surge prevention in the
control section.
Active demand limit manually overridden on MAINSTAT table.
Chiller is running under Ice Build temperature control.
G. NORMAL RUN WITH OVERRIDES
PRIMARY
MESSAGE
RUN CAPACITY
LIMITED
SECONDARY
MESSAGE
HIGH CONDENSER
PRESSURE
121
RUN CAPACITY
LIMITED
HIGH MOTOR
TEMPERATURE
122
RUN CAPACITY
LIMITED
LOW EVAP
REFRIG TEMP
123
RUN CAPACITY
LIMITED
HIGH COMPRESSOR
LIFT
124
RUN CAPACITY
LIMITED
MANUAL GUIDE
VANE TARGET
125
RUN CAPACITY
LIMITED
LOW DISCHARGE
SUPERHEAT
STATE
120
ALARM MESSAGE
PRIMARY CAUSE
120->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
121->Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.
122->Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
123->Surge Prevention
Override: Lift Too High For
Compressor.
124->Run Capacity Limited:
Manual Guide Vane Target.
No messages.
ADDITIONAL
CAUSE/REMEDY
Check for high condenser water temperatures.
Check setting in SETUP1.
Check
Check
Check
Check
Check
motor cooling lines.
for closed valves.
setting in SETUP1.
refrigerant charge.
for low entering cooler temperatures.
Check for high condenser water temperatures or low
suction temperature.
Target guide vane point has been forced in
MAINSTAT screen. Release force to continue normal
operation.
Check oil charge.
Check refrigerant charge.
*[LIMIT] is shown on the CVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault condition.
H. OUT-OF-RANGE SENSOR ALARMS
STATE
260
261
262
263
264
265
266
267
268
269
270
PRIMARY
MESSAGE
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SENSOR
FAULT
SECONDARY
MESSAGE
LEAVING CHILLED
WATER
ENTERING CHILLED
WATER
CONDENSER
PRESSURE
EVAPORATOR
PRESSURE
COMPRESSOR
BEARING TEMP
COMPRESSOR
MOTOR TEMP
COMP DISCHARGE
TEMP
OIL SUMP TEMP
COMP OIL
PRESS DIFF
CHILLED WATER
FLOW
COND WATER
FLOW
ALARM MESSAGE
PRIMARY CAUSE
260->Sensor Fault:
Leaving Chilled Water
261->Sensor Fault:
Entering Chilled Water
262->Sensor Fault:
Condenser Pressure
263->Sensor Fault:
Evaporator Pressure
264->Sensor Fault:
Comp Thrust Bearing Temp
265->Sensor Fault:
Comp Motor Winding Temp
266->Sensor Fault:
Comp Discharge Temp
267->Sensor Fault:
Oil Sump Temp
268->Sensor Fault:
Oil Pump Delta P
269->Sensor Fault:
Chilled Water Delta P
270->Sensor Fault:
Cond Water Delta P
75
Check
Check
Check
Check
Check
ADDITIONAL
CAUSE/REMEDY
sensor resistance or voltage drop.
for proper wiring.
sensor resistance or voltage drop.
for proper wiring.
sensor wiring.
Check sensor wiring.
Check
Check
Check
Check
Check
Check
Check
Check
Check
sensor resistance or voltage
for proper wiring.
sensor resistance or voltage
for proper wiring.
sensor resistance or voltage
for proper wiring.
sensor resistance or voltage
for proper wiring.
sensor wiring and accuracy.
Check sensor wiring and accuracy.
Check sensor wiring and accuracy.
drop.
drop.
drop.
drop.