Download Accel AV316 System information
Transcript
Table 15 — PIC 5 Alarm Codes (cont) ALARM CODE (ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PROTECTIVE LIMITS (CONT) The Cond Sat Refrig Temp is less than the Condenser Freeze Point. Check Condenser Freeze Point in configuration. Alm-262 ALM-262 Protective Manual Limit — Condenser Freeze Unit shuts down. Condenser water too cold or chiller shut down with brine below 32 F (0° C) in cooler so equalization temperature in chiller approached 32 F (0° C). Check condenser pressure transducer and wiring to IOB. Check condenser water temperature sensors and wiring to IOB. Check refrigerant charge. REFRIGERANT LEAK OPTION is Enabled and the REFRIGERANT LEAK SENSOR output exceeded REFRIGERANT LEAK ALARM mA. Check for refrigerant leaks. Alm-265 ALM-265 Protective Limit — Refrigerant Leak Check leak detector for proper operation. Manual Unit shuts down. Check REFRIGERANT LEAK ALARM mA setting in the OPTIONS screen. Check 4 to 20 mA or 1 to 5 v output from refrigerant leak sensor to IOB. Alm-266 ALM-266 Protective Limit — IOB Low Voltage Automatic Unit shuts down. Confirm that IOB SW2 dip switch 1 is in the correct position. Check IOB 24 VAC power supply and the transformer output voltage. Alarm before start indicates guide vane opening has not closed to less than 4%. Alarm while running indicates guide vane position is < -1% or > 103%. Alm-267 ALM-267 Protective Limit — Guide Vane Fault Manual Unit shuts down. Enter Quick Test and conduct Guide Vane Calibration. Check wiring between the guide vane feedback potentiometer and IOB terminals. Check the 10,000 ohm guide vane position feedback potentiometer or 4 to 20mA current. Check damper valve wirings. Alm-268 ALM-268 Protective Limit — Damper Valve Fault Manual Unit shuts down. Alm-269 ALM-268 Protective Manual Limit — HGBP Valve Fault Unit shuts down. Alm-270 ALM-270 Protective Limit — High Cond Water Flow Manual Unit shuts down. Check condenser water pressure sensor and wirings. Alm-271 ALM-271 Protective Limit — Emergency Stop Automatic Unit shuts down. Check EMSTOP command from network and the remote stop dry contact from IOB. 39 Do a control test on the damper valve to check the feedback signals. Check HGBP valve wirings. Do a control test on the HGBP valve to check the feedback signals.