Technical Manual Cold Storage Controllers TKP / TKC x130 - x140
Page 21
Adding controller units to extend cold storages
If one controller unit has not enough ressources to control a cold storage,
you can add one or more units. The necessary communication is made
by the digital inputs.
Each of the digital inputs can be assigned to the following jobs:
Refrigeration Lock (avtive low):
The refrigeration function of the
controller unit will be stopped as long
as 0Vare connected to the control
input.
Refrigeration Lock (avtive high): The refrigeration function of the
controller unit will be stopped as long
as mains voltage is connected to the
digital input.
Forced Refrigeration (active low):
The refrigeration function of the controller unit
will be forced as long as 0Vare connected to
the digital input.
Forced Refrigeration (active high):
The refrigeration function of the controller unit
will be forced as long as mains voltage is
connected to the digital input.
Principle of adding controller units:
solenoidvalve
or
compressor
defrostheater
solenoidvalve
or
compressor
defrost
1
defrost
1
defrostheater
optional
limitationsensor
refroferationrelay
forced refrigeration
led controller unit
(slave)
external defrost
defrostrelay
forced refrigeration
refrigerationrelay
external defrost
refrigeration
lock
leading controller unit
(master)
optional
limitationsensor
controlsensor
RS-485-data connection
led controller unit
(slave)
solenoidvalve
or
compressor
refrigerationrelay
defrost
1
defrost
1
defrostheater
The leading unit engages the cooling function of the 'slave'-units via their digital input 'Forced Refrigeration'. The 'slave'-units disable the cooling
function at the 'master'-unit via its digital input 'Refrigeration Lock', as long as a defrost function works.