Download Purebits x4 Technical data
Transcript
B8976060/02 Communication with Global I/Os ➣ GP and ZP/DP input areas must not overlap. ➣ GP and ZP/DP output areas must not overlap. ➣ The reserved input area for GP and ZP/DP must not include gaps. ➣ The reserved output area for GP and ZP/DP must not include gaps. ➣ The input area per station for GP and ZP/DP together must not exceed a maximum of 256 bytes. ➣ The output area per station for GP and ZP/DP together must not exceed a maximum of 256 bytes, of which a maximum of 64 bytes are reserved for GP. Input and output I/O areas can be selected independent of each other (refer to Fig. 9.12). They can be shifted "up" or "down". ☞ The I/O area reserved for the GP and ZP/DP must not be used by other I/O modules. An online modification of the GP or ZP/DP area only becomes effective after the CP 5430 TF has gone through power off/power on. 9 - 27 Volume 1