Download Siemens RDF301 Technical data
Transcript
3.9 Multifunctional input, digital input The thermostat has 2 multifunctional inputs X1 and X2. An NTC type sensor like the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 + P39 for X1 and P40 + P41 for X2. K NX The current temperature or state of the inputs X1/X2 is available on bus for monitoring purposes. R The parameters can be set to the following values: # 0 1 2 K NX Function of input Not used External / return air temperature Heating / cooling changeover R Heating/ cooling changeover Description No function. Sensor input for external room temperature sensor or return air temperature sensor to acquire the current room temperature, or floor heating temperature sensor to limit the heating output. Note: The room temperature is acquired by the built-in sensor if the floor temperature limitation function is enabled via parameter P51. Sensor input for "Automatic heating / cooling changeover" function. A switch can also be connected rather than a sensor Important: Switch closed means always cooling, (this cannot be changed), see section 3.5. Type X1/X2 -AI AI / DI Heating / cooling changeover is also possible via bus. In this case, the function must not be assigned to any local input X1, X2. See also section 3.5. Diagnostic value 00 is displayed for closed contact / 100 for open contact, if a switch is connected. 3 K NX Window contact 1) (RDF600KN) R Window state (RDF600..) 3 K NX Operating mode switchover (RDF301..) R Window state (RDF301..) 4 Dew point monitor Window contact input to switch the operating mode to Protection. If the window contact is open, user operations are ineffective and "OFF" is displayed. Window contact is also possible via bus. In this case, the function must not be assigned to any local input X1, X2. See also section 3.2.1. Digital input to switch over the operating mode to Economy. If the operating mode switchover contact is active, user operations are ineffective and "OFF" is displayed. Operating mode switchover is also possible via bus. In this case, the function must not be assigned to any local input X1, X2. See also section 3.2.1. Digital input for a dew point sensor to detect condensation. Cooling is stopped if condensation occurs. DI DI DI 49 / 92 Siemens Building Technologies RDF301, RDF301.50..., RDF600KN Functions Basic documentation CE1P3171en 2014-05-23