4.7.3
2-pipe fan coil unit
On 2-pipe applications, the thermostat controls a valve in heating / cooling mode
with changeover (automatic or manual), heating only, or cooling only. Cooling only
is factory set (P01 = 1).
ON/OFF control
The diagrams below shows the control sequence for 2-position control.
Heating mode
Cooling mode
Y
3076D01
Y
Y1
1
3076D02
Control sequence
on/off output
Y1
1
w
0
T[°C]
½ SDH
½ SDH
w
0
T[°C]
½ SDC
½ SDC
T[°C] Room temperature
SDH
Switching differential “Heating” (P30)
w
Room temperature setpoint
SDC
Switching differential “Cooling” (P31)
Y1
Control command “Valve” or “Compressor”
Modulating control: 3-position, PWM or DC 0…10 V
The diagrams below show the control sequence for modulating PI control.
Heating mode
Cooling mode
100
Y1
0
XpH
Note
3076D03
Y [%]
Y [%]
Y1
3076D04
Control sequence
modulating output
100
w
T[°C]
0
T[°C]
w
XpC
T[°C]
Room temperature
XpH
Proportional band “Heating” (P30)
w
Room temperature setpoint
XpC
Proportional band “Cooling” (P31)
Y1
Control command “Valve”
The diagrams only show the PI controller’s proportional part.
Setting the sequence and the control outputs
Refer to sections 4.5 ("Applications"), 4.7.1 ("Sequences") and 4.7.2 ("Outputs").