Troubleshooting by Indication on the Remote Controller SiUS34-907 Troubleshooting Caution Be sure to turn off the power switch before connecting or disconnecting the connector, or parts may be damaged. Imbalance in supplied voltage is in excess of 14 V (Y1). *1 YES Open phase? NO YES Open phase Normalize field cause. NO Fix power supply voltage imbalance. Is the voltage imbalance applied to the inverter in excess of 14 V (Y1)? YES NO <When voltage monitoring is possible:> Using a device capable of constant recording of power supply voltage record power supply voltage between 3 phases (L1 ~ L2, L2 ~ L3, L3~L1) for about one continuous week. No abnormalities are observed in the power supply, but the imbalance in voltage recurs. Part or wiring defect After turning the power supply OFF, check and repair the main circuit wiring or parts. (1) Loose or disconnected wiring between power supply and inverter (2) Loose or disconnected noise filter Power supply voltage imbalance Even if the power supply voltage is not unbalanced when measuring it, there are many cases where it gets unbalanced during nighttime (around 6:00PM to 10:00PM). measure Replace the inverter PCB. Explanation for users *In accordance with "notification of inspection results" accompanying spare parts. Be sure to explain to the user that Give the user a copy of "notification of inspection results" and leave there is a "power supply imbalance" it up to him to improve the imbalance. for which DAIKIN is not responsible. *1.Measure voltage at the X1M power supply terminal block. 170 Troubleshooting