Download Daikin R-410A Specifications
Transcript
Basic Control 2.2 SiUS39-601 Compressor PI Control Compressor PI Control Carries out the compressor capacity PI control to maintain Te at constant during cooling operation and Tc at constant during heating operation to ensure stable unit performance. [Cooling operation] Controls compressor capacity to adjust Te to achieve target value (TeS). Te setting L M (Normal) H (factory setting) 37.5 43 48 Te : Low pressure equivalent saturation temperature (°F) TeS : Target Te value (Varies depending on Te setting, operating frequency, etc.) [Heating operation] Controls compressor capacity to adjust Tc to achieve target value (TcS). Tc setting L M (Normal) H (factory setting) 109.5 115 120 34 Tc : High pressure equivalent saturation temperature (°F) TcS : Target Tc value (Varies depending on Tc setting, operating frequency, etc.) Function