SELECT LOCATION FOR AIR CLEANER Remember to select a location that is readily accessible for periodic inspection and cleaning of this air cleaner. Allow a minimum of 24" clearance in front and 12" clearance above the air cleaner for component removal and service space. For complete dimensions required refer to the section entitled UNIT DIMENSIONS. DIRECTION OF AIR FLOW THROUGH THE AIR CLEANER This air cleaner is set up for left to right air flow when you are facing the access door. For right to left air flow, follow these directions: 1. Remove the prefilter(s) and cells from the cabinet. A plastic positioning spacer is located inside the bottom of the cabinet. This spacer is secured to the cabinet using a #6-32 round head Phillips drive thread cutting screw to assure installation of the cells in the proper position with respect to air flow (Figure 6). 2. Remove the screw and reposition the spacer in the alternate hole at the bottom of the cabinet. 3. Replace the screw to insure the plastic spacer is not accidentally knocked out of place during normal maintenance. It must be installed in the hole provided closest to the air leaving side of the cabinet. Seal the unused hole with duct tape. 4. Remove the cell handle and reattach to the opposite end of the cell. Turn cells around, replace in cabinet and replace prefilters on the air entering side. The directional arrows on the cell end plates must point in the direction of air flow. 19