• Water cooled installation procedure 1 Installation of outdoor units 1-9 Refrigerant piping 1-9-8 Additional refrigerant charge NOTE Procedures for charging additional refrigerant. [Heat pump system] [Heat recovery system] 햲 Pressure reducing valve 햳 Nitrogen 햴 Refrigerant tank 햵 With a siphon 햶 Measuring instrument 햷 Vacuum pump 햸 Val ve A 햹 Val ve B 햺 Charge hose 햻 Outside unit 햽 Gas side 햾 Liquid side 햿 Discharge gas side 헀 Suction gas side 헁 Shutoff valve service port 헂 To indoor unit 헃 To indoor units / BS units 헄 Dotted lines represent onsite piping • VRV® Systems • Installation procedure 29