Download Directed Electronics MERLIN 2000 Specifications

Transcript
The Modbus Protocol (continued)
Guide to Integration
Modbus / Jbus
Each frame includes four types of information:
b Slave number (1 byte):
v the slave number specifies the destination slave (1 to 255). If this number is zero,
the query is addressed to all slaves and there is no response message.
b Function code (1 byte):
v can be used to select a command (read, write, bit, word) and to verify if the
response is correct.
b Information field (n bytes):
v contains the parameters associated with the function: bit address, word address,
bit value, word value, number of bits, number of words.
b Control word (2 bytes):
v is used to detect transmission errors.
All exchanges except broadcasting include
two frames: a query from the master and a
response from the slave.
Broadcast exchanges (write only) consist of
only one frame from the master.
Diagram showing how the transmission medium is filled
E52351
Analysis of the response
and preparation of
the next exchange
D
D
Master
R
Slave N°1
R
Slave N°n
Physical
medium
Exchange i-1
D
Query
Exchange i
R
Time
Exchange i+1
Response
Wait
Broadcast
Turnaround
time
Execution by slave
Note: The lengths of QUERY, RESPONSE, BROADCAST, WAIT and
PROCESSING depend on the function performed.
Schneider Electric
59