SQ: 1-30 If a nonredundant Coordinator Processor card is disabled on a running process, all operator process changes, links between controllers in that cage, and links to and from that ControlFile will freeze at the last value received. The controller will continue to operate the process under these conditions. As soon as the Coordinator Processor is restarted, all links will be updated. If a Controller Processor card is disabled on a running process, the analog output Field interface card and the discrete output module will either hold their last value or go to zero, depending on the position of the jumper on the Field interface card. If it is necessary to close (go to zero) the output of the field device that uses the ”HOLD” mode after the controller is disabled, the Field Interface card must be removed. If both PeerWay Buffer cards are removed from the ControlFile on a running process, all operator changes and links to and from this ControlFile will freeze at the last value received. The links within the ControlFile will continue to update. The Controller Processors will continue to operate under these conditions. RS3: Service Quick Reference Guide Troubleshooting