APPENDIX G
UL DATA
CAUTION
To operate this charger from inputs other than 120 Vac, you must
use branch circuit protection. To reduce the risk of fire, use only
on circuits provided with the following branch circuit protection
in accordance with the National Electrical Code, ANSI/NFPA 70.
Current
Rating
12 Adc
16 Adc
20 Adc
25 Adc
Charger Voltage Rating
48 Vdc
130 Vdc
48 Vdc
130 Vdc
--25A
--20A
15A
25A
12A
20A
20A
30A
15A
30A
25A
40A
20A
35A
208 Vac Branch Circuit
240 Vac Branch Circuit
Protection (Amperes)
Protection (Amperes)
NOTE: This table does not apply to AT10.1 chargers with 480 Vac input.