Download AT30 - Eagle Eye Power Solutions
Transcript
OPERATING THE AT30 2.3.8. Using the Low Level Detector (LLD) The AT30 is equipped with a summary (common) alarm relay safety override circuit. This feature forces the alarm relay contact to transfer, sending an alarm, even if there is a catastrophic failure of the AT30 control circuitry. A low battery voltage triggers the safety circuit. Main Control PC Board (A1) hardware, not software, maintains the low level detect circuit. Therefore, to remotely monitor this alarm, user connections must be made at terminal block (TB3). The summary alarm contacts (TB4) on the Auxiliary Alarm Relay PC Board will not signal a low level detect alarm. If you have a dc power supply, you can adjust the battery voltage that triggers the alarm. On the back of the Main Control PC Board (A1), find the potentiometer RA1, as shown in the figure below. Disconnect all ac and dc power sources from the AT30, and connect your dc power supply to the dc output terminals of the charger (positive to positive and negative to negative). Adjust the power supply to the voltage at which you want to activate the alarm. NOTICE You need at least 50% of the nominal output voltage to power the AT30 Main Control PC Board (A1). Adjust RA1 with a small jeweler's screwdriver clockwise until the alarm just activates. A red LED indicator (DS10) next to RA1 indicates when the alarm is active. 38