Download Modbus for Field Technicians
Transcript
Modbus for Field Technicians 8. MODBUS AND GATEWAYS A gateway is a device that makes data read using one protocol available using another protocol. For example you could read Modbus data from a power meter and serve that data using BACnet to a Building Automation System. What data must the gateway report if the Modbus is offline or the data cannot be read? It can report the last value read. How old is that value? In this example, we can exploit a property of each BACnet data object called Reliability. When the validity of the data is unknown, like when a field device is offline, we mark the BACnet objects as unreliable. Now a consumer of that data has enough information – he knows the value and if it is reliable. It is his call whether to use the data or not. Modbus does not have an equivalent mechanism. If a gateway is doing the opposite, for example, reading BACnet data and serving that data using Modbus. If the BACnet link is broken the data validity is questionable. However, in Modbus there is no way of reporting this. The gateway can take one of two actions – serve the invalid data or – not serve the data – by not responding to the poll. This is the strategy FieldServer gateways use. If the Data is invalid, the Gateway does not respond to a request for that data and allows the client to time out. Page 17