Download Dimplex LA 16 MI Technical data
Transcript
Heat pump for heating purposes – air source – outdoor installation High-efficiency air-to-water heat pump package solution Heating and domestic hot water preparation package Max. flow temperature for heating 58 °C Casing colour white aluminium Heat pump and HWK 332 Econ hydro tower HPL..TUW The Hydro Tower with integrated WPM EconPlus regulation enables the fast and simple connection of an air-to-water heat pump installed outdoors to a heating system with an unmixed heating circuit. The following components are mounted and wired in a spacesaving way inside a single casing. • Switchable pipe heater (2/4/6 kW) • Safety valve incl. connection for an expansion vessel • Buffer tank (100 l) with installation option for an additional immersion heater (up to CTHK 634). • Hot water cylinder (300 l) with installation option for an additional heating element (flange heater). • Electronically regulated circulating pump (energy-efficiency class A) pre-wired with coupling relay for an unmixed heating circuit (consumer circuit). • Unregulated circulating pump integrated for the generator circuit and hot water circulating pump. • The hydraulic isolation of the generator circuit and the consumer circuit is done via two differential pressureless manifolds (bypass pipes), which are each fitted with a check valve. The unregulated circulating pump in the generator circuit is only operated when the compressor is running in order to reduce the runtimes. The uniform flow through the buffer tank connected in series extends the runtimes of the compressor and ensures the required heating water flow in all operating situations. Electrical connection cable EVL . . U between heat pump and heat pump manager must be ordered separately. Lower operating limit heat source (heating operation) -25 °CUpper ; operating limit heat source (heating operation) 35°C; Refrigerant R404AConnection ; heating 1¼⬙; Connection voltage 3/N/PE ~400 V, 50 Hz Order reference Art.-Nr. Heatoutput kW Features Weight kg HPL9TUW 362630 7.5kW ackage P LA 9TU with HWK 332 Econ hydro tower 418 HPL12TUW 362640 9.4kW ackage P LA 12TU with HWK 332 Econ hydro tower 490 HPL17TUW 362650 14.6kW ackage P LA 17TU with HWK 332 Econ hydro tower 446 Heat output according to EN 14511 at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C) The technical data for the heat pump can be found on the following pages. The sales package consists of a high-efficiency heat pump without WPM EconPlus and the HWK 332 Econ hydro tower with integrated heat pump manager. The HWK 332 hydro tower (without integrated HPM) can be ordered for use in combination with air-to-water heat pumps from the LA. . . AS/PS series. If the heating water connection lines are more than 10 m long, the free compression values stated in the device information must be observed (minimum pipe diameter for volume flows of more than 1. 5 m³/h: DN 32)! HPL9TUW 12TUW 17TUW 4 362630 362640 362650 4015627362635 4015627362642 4015627362659 www.dimplex.de/en 2010