Transcript
TC12 Installation, Commissioning & Maintenance Handbook KAD 3 = 2 KAD 4 = 3 :sensor 3 is phase C :sensor 4 is phase D Select normal lamp monitoring (not RLM) on vehicle phases: Note: Sensors 3 and 4 do not monitor vehicle phases and so their configuration does not need to be changed. KRE 1 = 0 KRE 2 = 0 :sensor 1 :sensor 2 Example 4 - Pelican (single current sensor) Description: This is a pelican controller with dimming. In this example, the pelican is monitored with a single current sensor (see example 5 for separate wait and pedestrian and vehicle monitoring using three current sensors) The configuration commands are detailed below. Enable LMU write access: AMB = 35 NEC = 249 Allocate function of current sensor 1: KPT 1 = 11 :the current sensor monitors a complete :pelican stream Allocate the mains state inputs associated with each current sensor: Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0 to 31 on the handset commands. KMS 0 1 = 31 KMS 1 1 = 30 KMS 2 1 = 29 :sensor 1 vehicle green is on digital input 32 :sensor 1 pedestrian green is on digital input 31 :sensor 1 wait is on digital input 30 Allocate aspect drive identity to each current sensor: KAD 1 = 0 :sensor 1, vehicle is phase A (and so by implication, the pedestrian is phase B) Example 5 - Pelican (three current sensors) Description: 666/HE/43100/000 This is a pelican controller with dimming. Page 123 Issue 10