Download Sharp R-426H Technical data
Transcript
4. Service procedures (J) Change the period of the filter timer ❏ If the period of filter timer is not suitable (for example in case of dirty environment), the period can be shortened to half as follows: a Press the TEST / CHK button for more than 4 seconds. AIR FLOW UNIT FLAP MODE UNIT No. R.C. No. CODE No. SET TEMP. TIMER SET FAN SPEED SETTING SET DATA SET CL ON • OFF • TEST / CHK 0213_M_I b In case of group control, if you want to change all units in group control collectively, proceed next step remaining “ALL” displayed. If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button. c Select the CODE No. 02 with , d Change the No. from 0 to 1 with AIR FLOW UNIT FLAP , ( No. CODE No. SET TEMP. SET TEMP. FAN SPEED 1 ) button. EX: UNIT No. 1–6 CODE No. 02 T type 150 hr → MODE UNIT No. R.C. (SET TEMP) button. 75 hr 2 TIMER SET SETTING SET DATA SET CL ON • OFF • 3 TEST / CHK 0214_M_I e Press the SET button. CODE No. 06, SET DATA and SETTING change from flashing to ON state. 4 f If you made a mistake, press the CL button. g Finally, press the TEST / CHK button. 5 IV - 35