I/O Modules Process Data Architecture for MODBUS/TCP • 261 4 Channel Analog Input Modules 750-453, -455, -457, -459, -460, -468, (and all variations), 753-453, -455, -457, -459 Input Process Image Offset 5.2.4 Byte Destination Remark High Byte Low Byte 0 D1 D0 Measured Value Channel 1 1 D3 D2 Measured Value Channel 2 2 D5 D4 Measured Value Channel 3 3 D7 D6 Measured Value Channel 4 Analog Output Modules The hardware of an analog output module has 16 bits of measured analog data per channel and 8 bits of control/status. However, the coupler/controller with MODBUS/TCP does not have access to the 8 control/status bits. Therefore, the coupler/controller with MODBUS/TCP can only access the 16 bits of analog data per channel, which are grouped as words and mapped in Intel format in the Output Process Image. When digital output modules are also present in the node, the analog output data is always mapped into the Output Process Image in front of the digital data. 2 Channel Analog Output Modules 750-550, -552, -554, -556, -560, -585, (and all variations), 753-550, -552, -554, -556 Output Process Image Offset WAGO-I/O-SYSTEM 750 BACnet/IP Controller Byte Destination Remark High Byte Low Byte 0 D1 D0 Output Value Channel 1 1 D3 D2 Output Value Channel 2