Download Code Alarm F65 Specifications
Transcript
www.pulsar.pl PowerSecurity APPENDIX B – FAILURE CODES OF THE PSBEN 27,6V POWER SUPPLY Failure code Information Technical output activation F01 No AC power! EPS FLT F02 AUX Fuse! PSU FLT F03 BAT fuse! APS FLT F04 Output overload!! PSU FLT F05 Faulty battery! F06 High AUX voltage! F07 High battery voltage! PSU FLT F08 Battery charging circuit failure! PSU FLT F09 Low AUX voltage! PSU FLT F10 F11 F12 F13 F50-F54 F60 F61-F64 F65 Event code I00 I01 I02 I03 I04 I05 I06 Low battery voltage! Low battery voltage – off! EXT external input! PSU enclosure opening! Internal damage of the PSU. No communication LCD damage Causes, comments - No AC mains supply - FMAIN fuse failure - Blown FAUX fuse - AUX output overload - Blown FBAT fuse - Short circuit in the battery circuit - Short circuit in the AUX output circuit - PSU overload - Worn out batteries - Undercharged batteries - Battery not connected APS FLT PSU FLT - The output voltage of the PSU over 29.4V - Battery voltage >28V - The output voltage of the PSU set too low , below 26V - Battery charging circuit failure - The output voltage below 23,6V (during buffer operation) - The battery voltage has dropped below 23V (during battery-assisted operation) - the battery voltage has dropped below 20V (during battery-assisted operation) - Activation of the input of collective failure: EXTi APS FLT APS FLT ALARM PSU FLT PSU FLT - service codes PSU FLT - no communication with LCD panel PSU FLT - service codes Access unlocked - passwords unlocked Description PSU start-up AC power restored AUX fuse replaced BAT fuse replaced Battery status: OK Battery test – START Enclosure closed 22