Download Emerson Liebert IntelliSlot Unity Communications Interface Card Technical Specifications

Transcript
BACnet Communications - Thermal Management Products
Table 82
Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™,
Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX™ - Analog Data
Controller Liebert iCOM® v4
Object Type
Data Label
Instance
Object Name
Access
Notes
Extra
Notes
Liebert Condensers - Condenser 2 Fan 2
Condenser Fan Speed
Analog_Value
2023
5276_1_2_2
RD
Units: %
4, 9
Condenser Fan Power
Analog_Value
2031
5538_1_2_2
RD
Units: kW
4, 9
Liebert Condensers - Condenser 2 Fan 3
Condenser Fan Speed
Analog_Value
2024
5276_1_2_3
RD
Units: %
4, 9
Condenser Fan Power
Analog_Value
2032
5538_1_2_3
RD
Units: kW
4, 9
Liebert Condensers - Condenser 2 Fan
Condenser Fan Speed
Analog_Value
2025
5276_1_2_4
RD
Units: %
4, 9
Condenser Fan Power
Analog_Value
2033
5538_1_2_4
RD
Units: kW
4, 9
Actual Cold Aisle Humidity
Analog_Value
2044
6085_1
RD
Units: % RH
—
Actual Cold Aisle Temperature
Analog_Value
2045
6086_1
RD
Units: deg C
—
Actual Cold Aisle Temperature
Analog_Value
12045
6086_1_deg_F
RD
Units: deg F
—
Cold Aisle Cascade Fan
Speed Max Set Point
Analog_Value
2046
6087_1
RD
Units: %
—
Cold Aisle Fan Speed Min Set
Point
Analog_Value
2047
6088_1
RD
Units: %
—
Cold Aisle Fan Speed Max Set
Point
Analog_Value
2048
6089_1
RD
Units: %
—
Humidification Fan Speed Min
Set Point
Analog_Value
2049
6096_1
RD
Units: %
—
Heating Fan Speed Min Set
Point
Analog_Value
2050
6097_1
RD
Units: %
—
Dehumidification Fan Speed
Min Set Point
Analog_Value
2051
6098_1
RD
Units: %
—
Back Draft Control Fan Speed
Analog_Value
2052
6099_1
RD
Units: %
—
PDX
Table 83
Number
Extra Notes to Table 82
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.29.03R
4
This point is supported on:
iCOM controller version 2.01.29.06R
5
This point is supported on:
iCOM controller version 2.01.40R
6
This point is supported on:
iCOM controller version 2.02.21R
7
This point is supported on:
iCOM controller version 2.03.27.06R
8
This point is supported on:
iCOM controller version 2.03.32R
9
This point is supported on:
iCOM controller version 2.03.33R
Liebert® IntelliSlot® Modbus/BACnet
264