Download Emerson Liebert IntelliSlot Unity Communications Interface Card Technical Specifications
Transcript
BACnet Communications - Thermal Management Products Table 82 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX™ - Analog Data Controller Liebert iCOM® v4 Object Type Data Label Instance Object Name Access Notes Extra Notes Liebert Condensers - Condenser 2 Fan 2 Condenser Fan Speed Analog_Value 2023 5276_1_2_2 RD Units: % 4, 9 Condenser Fan Power Analog_Value 2031 5538_1_2_2 RD Units: kW 4, 9 Liebert Condensers - Condenser 2 Fan 3 Condenser Fan Speed Analog_Value 2024 5276_1_2_3 RD Units: % 4, 9 Condenser Fan Power Analog_Value 2032 5538_1_2_3 RD Units: kW 4, 9 Liebert Condensers - Condenser 2 Fan Condenser Fan Speed Analog_Value 2025 5276_1_2_4 RD Units: % 4, 9 Condenser Fan Power Analog_Value 2033 5538_1_2_4 RD Units: kW 4, 9 Actual Cold Aisle Humidity Analog_Value 2044 6085_1 RD Units: % RH — Actual Cold Aisle Temperature Analog_Value 2045 6086_1 RD Units: deg C — Actual Cold Aisle Temperature Analog_Value 12045 6086_1_deg_F RD Units: deg F — Cold Aisle Cascade Fan Speed Max Set Point Analog_Value 2046 6087_1 RD Units: % — Cold Aisle Fan Speed Min Set Point Analog_Value 2047 6088_1 RD Units: % — Cold Aisle Fan Speed Max Set Point Analog_Value 2048 6089_1 RD Units: % — Humidification Fan Speed Min Set Point Analog_Value 2049 6096_1 RD Units: % — Heating Fan Speed Min Set Point Analog_Value 2050 6097_1 RD Units: % — Dehumidification Fan Speed Min Set Point Analog_Value 2051 6098_1 RD Units: % — Back Draft Control Fan Speed Analog_Value 2052 6099_1 RD Units: % — PDX Table 83 Number Extra Notes to Table 82 Description 1 This point is supported on: iCOM controller version 1.04.042.STD 2 This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) 3 This point is supported on: iCOM controller version 2.01.29.03R 4 This point is supported on: iCOM controller version 2.01.29.06R 5 This point is supported on: iCOM controller version 2.01.40R 6 This point is supported on: iCOM controller version 2.02.21R 7 This point is supported on: iCOM controller version 2.03.27.06R 8 This point is supported on: iCOM controller version 2.03.32R 9 This point is supported on: iCOM controller version 2.03.33R Liebert® IntelliSlot® Modbus/BACnet 264