• • • Observe technical information, local installation requirements and general regulations. To vent the JUDO PROFIMAT Automatic Backwash Protective Filter, perform backwash immediately after installation. For information on the electrical connection of the potential-free input or output signals, please refer to the terminal diagram. 4.3 Design of the Backwash Connection The dimensions of the conduit cross section for backwash water should be based on specific local features, for example the inclination of the wastewater pipeline, number of bends, length of the wastewater line, etc. It must be ensured at all times, including the case of a technical malfunction, that wastewater can be removed without causing any damage. The backwash flow volume with a JUDO PROFIMAT Automatic Backwash Protective Filter is 0.5 to 1.5 litres per second (8 to 25 gpm) with the flushing valve completely open and approximately 29 to 43 psi (200 to 300 kPa) of water pressure. For backwash time, see the table in Technical Data. With all options for removing the backwash water, make certain to allow for free discharge. creation date: 6/12/2006 release date: amendment date: 3/19/2008 version: 2008/03 JUDO Water Treatment Inc. 2060 Steeles Ave. West, Unit#4 Concord, Ontario L4K 2V1 Operating Instructions: JPF-A/TP DN125-DN200 (5” – 8”) GB CDN Tel. (905) 761-1555 • Fax (905) 761 - 3335 e-mail: service@judo-online.com • www.judo-online.com Changes in the interest of the technical progress reserve! 13-24