Graphic Data Manager/Modbus Slave
__________________________________________________________________________________
3.2.8.2
Ending a batch
If the user administration function is enabled, an ID (max. 8 characters) and a name (max. 20 characters) must
be transmitted, separated by a ';'. If an uneven number of characters is sent, a blank (0x20) must follow.
Example:
End batch 2, user administration function enabled (ID: "IDSPS", Name "RemoteX")
Byte
0
func
2
1
no.
2
2
49
'I'
3
44
'D'
4
53
'S'
5
50
'P'
6
53
'S'
Register
3088
3089
3090
3091
3092
3093
3094
3095
7
3B
';'
8
52
'R'
9
65
'e'
10
6D
'm'
11
6F
'o'
12
74
't'
13
65
'e'
14
58
'X'
15
20
‚’
Value
(hex)
0202
4944
5350
533B
5265
6D6F
7465
5820
Query:
Slave address
Function
Register
No. of registers
No. of bytes
Data
CRC
05
10
16: Write Multiple Register
0C 10
Register 3088
00 08
8 registers
10
16 bytes
02 02 49 44 53 59 53 3B 52 65 6D 6F 74 65 58 20
D3D6
Response:
Slave address
Function
Register
No. of registers
CRC
05
10
0C 10
00 08
C2 DE
16: Write Multiple Register
Register 3088
8 registers
The entry "Batch 2 terminated" and "Remote (IDSPS)" is saved in the event list. This message also appears on the
screen for a few seconds.
59