SILAS Control Unit
Commissioning
Type A7-3741-1110/....
6.
Commissioning
6.1
General Settings for Commissioning
6.1.1
Purging Function
Various purging functions can be assigned to the SILAS control unit to suit the
application. The behaviour of the SILAS control unit changes depending on the purging
function selected.
The following table shows the possible functions:
Program
6.1.2
Functions
Purge time
necessary
Purge time
starts when P1
is exceeded
Purge time
stops once P4
is reached
K2 switches off
once the
internal
pressure drops
below the P1
level
PRG YES
Yes
No
No
No
PRG YP1
Yes
Yes
No
No
PRG YP2
Yes
Yes
No
Yes
PRG YP3
Yes
Yes
Yes
No
PRG NO
No
No
No
No
K3 Relay
Various functions can be assigned to the floating K3 relay. The following table shows the
possible functions:
Level
K2+
Release
P1+
MIN alarm
P1-
MIN alarm
P2+
P2P3+
Page 34 of 68
Function
Preliminary
alarm
Preliminary
alarm
Purging
pressure
P4+
Max alarm
PT+
Purge time
BYP
Bypass
ALR
Functions alarm
Switches simultaneously with K2
Switches on if the P1 pressure switching level is
exceeded
Switches on if the level drops below the P1
pressure switching level
Switches on if the P2 pressure switching level is
exceeded
Switches on if the level drops below the P2
pressure switching level.
Switches on if the P3 pressure switching level is
exceeded
Switches on if the P4 pressure switching level is
exceeded
Switches on when the purge time counts down
Switches on when the bypass is activated
Switches on if internal malfunctioning is detected.
Technical data subject to change without notice.