Download English

Transcript
SILAS Control Unit
Product Description
Type A7-3741-1110/....
2.6
Pressure Monitor
DANGER
DANGER due to deposits of dust.
When used in Dust Ex applications, deposits of dust can build up in the
pressure monitor.
 If a lot of dust accumulates, clean the pressure monitor twice a year.
The pressure monitor has two functions inside the SILAS control. Firstly, it serves as a
pressure control valve which opens if the internal pressure is too high and reduces the
excessive pressure. Secondly, an orifice is integrated in the pressure monitor which
determines the flow during the purge time.
The pressure monitor must be mounted separately from the SILAS control unit in the
pressurised enclosure.
2.7
Digital Purge Gas Valve
Warning
The digital purge gas valve is permitted only for operation with a
SILAS control unit which has a suitable valve fuse.
If the digital purge gas valve is operated with a control module which has
inadequate fusing, there is a risk that the valve fuse will be destroyed.
 Check that the purge gas valve is compatible with the SILAS
control unit.
The digital purge gas valve controls the supply of purge gas.
It is an upstream solenoid valve and its function is to introduce purge gas into a
pressurised enclosure for Zone 2.
Here, the digital purge gas valve is controlled by the SILAS control unit to allow the purge
gas valve to open to purge the pressurised enclosure and close again when the purging
is finished.
An integrated, adjustable leakage air needle compensates for the loss through leakage in
the pressurised enclosure.
Techncal data subject to change without notice.
Page 15 of 68