Download Installation- and Operating Instructions
Transcript
Installation- and Operating Instructions filter control PC-2000 page: 3 (22) operation this contact has to be closed at the latest 10 seconds after the filter pump has started, otherwise the filter pump will is switched off and the error signal light flashes. In the backwash operation this contact is not interrogated. The clamps drive mains voltage! Mains supply for use of a 230V three-phase current pump: Pool control PC-2000 17 18 15 16 W1V1 U1 N Protective winding M 1 Filter pump 230V max. 8A L3 L2 L1 N Pre-fuses max. B16A FI-switch 25A/0,03A Mains 1/N/ 230V 50Hz The factory-provided inserted bridge between the clamps 15 and 16 has to be removed if a pump with protective winding contact is connected. If no connection is carried out, it has to remain screwed in. The clamps drive mains voltage! Instead of the factory-provided bridge inserted between the clamps 17 and 18 it is possible to connect a flow monitor or a pressure controller. In the filter operation this contact has to be closed at the latest 10 seconds after the filter pump has started; otherwise the filter pump is switched off and the error signal light flashes. This contact is not interrogated in the backwash operation. The clamps drive mains voltage! So that the electronic motor protection operates properly, the motor current has to be led via all 3 contact points of the filter control (clamps L2 and L3 as well as U1 and V1 bridged, pump connected to W1).