Preparing for operation
MELSEC-WS
8.2 Wiring precautions
The wiring precautions are shown below.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
69
Use either port 1 or port 2 for star connection.
Use an Ethernet cable shown in Section 8.1.
The Ethernet cable has restrictions on the bend radius.
The maximum bend radius is four times of the cable outside diameter.
Place the cables in a duct or clamp them.
If not, dangling cable may swing or inadvertently be pulled, resulting in
damage to the module or cables or malfunction due to poor contact.
When laying the cables, do not touch the contact surfaces of the connector of
the cable and the connector of the module nor let dirt or dust collect on the
contact surfaces.
If oil from the hands, dirt, or dust adheres to the cores, the transmission loss
may increase, resulting in communication failure.
When connecting/disconnecting the cable to/from the module, hold the
connector part.
Connect the connectors of the cable and the module until they click.