Download COMETH-FIELD-RD USER'S GUIDE

Transcript
- 12 -
III.3 RS232 connector cabling J1
DB9 male with DTE cabling
PIN
1
2
3
4
5
6
7
8
9
Signal name
DCD
RxD
TxD
DTR
GND
DSR
RTS
CTS
RI
Direction
Input (to Cometh)
Input (to Cometh)
Output (from Cometh)
Output (from Cometh)
Digital ground
Input (to Cometh)
Output (from Cometh)
Input (to Cometh)
Input (to Cometh)
III.4 RS422/RS485 connector cabling J2
DB9 female
PIN
1
2
3
4
5
6
7
8
9
RS422
RS485
Connect together for Connect together for line
line polarization
polarization
B (-TxD)
Unused
B’ (-RxD)
BB’ (-TxD/RxD)
Digital ground
Digital ground
Connect together for Connect together for line
line polarization
polarization
A (+TxD)
Unused
A’ (+RxD)
AA’ (+TxD/RxD)
For COMETH-FIELD-RD rev A :
Terminating resistor enable
Connect the jumper to ON position
Terminating resistor disable
Connect the jumper to OFF position or left unconnected
For COMETH-FIELD-RD rev B :
Terminating resistor enable
Switch to ON position
Terminating resistor disable
Switch to OFF position
COMETH-FIELD-RD USER’S MANUAL (D
D
T
U
DT
TU