Measurement Methods
Illustration
The following illustration shows the loads
Export of
active power
Import of
active power
Import of
reactive
power
+
+
2
1
S
Q
M
P
Export of
reactive
power
7.1.1
-
3
4
Single Phase, 1-Element Metering
1- element metering in a 2-wire system
In a 2-wire installation a single phase meter is used. Normally the 2 wires are a
phase voltage and the neutral.
The active energy consumed by the load is the product of momentary voltage and
current integrated over the desired measuring time period.
Calculating active
power
In the case where no harmonics is present and the rms value of the voltage and
current is constant, the active power can be expressed as:
P = Urms*Irms *cos 
where  is the phase angle between the voltage and the current.
A43/A44
User Manual
82
2CMC484001M0201
Revision: A