C2-04
Operation
Supply should be filtered 12-32 Vdc,
maximum ripple <30% on full load.
Attention!
Wrong supply polarity can damage the
driver.
Attention!
Driver has no fuse in it.
Choose the current limit mode:
continuous / tripping
Trip jumper:
On = tripping limit
Off = continuous limit
Choose control mode
(forward / backwards)
pos = PNP positive control
neg = NPN negative control
Choose the ramp time
FORWARD
10ms
20ms
0
40ms
80ms
150ms
0.25s 0.5s 1s
Choose the current limit value / Amps.
4A
3A
OPERATIONAL EXAMPLE: tripping current limit
no delay between the start-ups (same direction)
FASTENING HOLES 3.2 mm
9V
FORWARD
2A
5 CONTROL
MODE
neg. pos.
no start-up to
the same direction
1A
TRIP
"off" "on"
I lim. =2 x set
RAMP.
66.5 mm
72.5 mm
CURRENT
after trip starts only to
the opposite direction
REVERSE
Attention!
The current limit values can
be affected by the used
motor.
In start-up the current
limit value is doubled
(for 0.3 seconds).
I lim = set
MOTOR
VOLTAGE
direction change
motor
brakes
start-up cycle 300ms
(ramp) 0-1s
motor brakes
delay 20ms
motor meets an obstacle
current trip cuts the voltage
OPERATION EXAMPLE: continuous current limit
FORWARD
REVERSE
4
+12-32V
SUPPLY
current limit x2
23 mm
5 mm
5 mm FREE SPACE
REQUIRED AT BOTTOM SIDE
I lim = set
MOTOR
VOLTAGE
start-up cycle 300ms
(ramp) 0-1s
motor meets an obstacle
driver limits the current
concens - ver 1.1 - January 2009 - Check updates on www.concens.com or www.concens.eu