8.1 Sensor Cartridge Replacement
If replacing a sensor cartridge with a different
gas type sensor cartridge the display will
scroll the message ‘ChAngE gAS?’ If you are
changing the sensor cartridge gas type press
‘3’ to accept. If not, fit the correct sensor
cartridge. The pass code (if set) must be
entered to change sensor cartridge gas type.
To set the correct gas for a multi gas type
sensor cartridge refer to Section 7.2.2.
Honeywell Analytics recommends that the sensor
cartridge be replaced without power to the Midas® unit.
If fitting a sensor cartridge to a unit that is powered,
please refer to Section 7.4.3 to inhibit the detector’s
outputs.
8.1.1 Sensor Cartridge Fitting/Replacement
1. U
nscrew the thumbscrew located on the
front panel and remove the cover by pulling
it forwards off the main chassis (see Diagram
27).
2. Ensure the power switch on the terminal
module is in the off position.
3. Remove the old sensor cartridge from the unit (if
fitted) by unclipping the two sensor cartridge locking
tabs located either side of the sensor cartridge and
using them to firmly pull the sensor cartridge out
(see diagram 23).
4. Fit the new sensor cartridge by aligning the
pins at the top of the sensor cartridge with the
socket in the sensor cartridge chamber.
5. Carefully push the sensor cartridge into the
sensor cartridge chamber until fully home and
lock in place using the tabs either side of the
sensor cartridge (see diagram 24).
6. Switch the power switch on the terminal
module to the ‘on’ position.
7. R efit the detector’s cover by aligning the
slots either side with the locating tabs on the
mounting bracket assembly and pushing the
cover horizontally until home. Tighten the
thumbscrew located on the front panel (see
diagram 25).
8. Confirm that the LCD messages “LOAd” and
“WArm” are replaced by a zero concentration
display. Confirm that the yellow fault LED is off.
Midas Technical Handbook
8-3
Diagram 8-1. Removing detector cover
REMOVING COVER
chassis
loosen
midas
Gas Senso
cover
r Cartri
dge
NITROGE
N TRIF
LUORIDE
PN : MIDNF3
AS-S-HFX
SN : 0234
4566
Use by
: 07-0 70
9-2006
mounting
bracket
Diagram 8-2. Removing sensor cartridge
sensor
midas
Gas Senso
r Cartr
idge
NITROGE
N TRIF
LUORIDE
PN : MIDNF3
AS-S-HFX
SN : 0234
4566
Use by
: 07-0 70
9-2006
zellw