Download JTL USER GUIDE CONTROLLER TYPE: LAPI
Transcript
Display Controlled Fans Only Mode The controller can be put into fans only mode using the display switch. This feature is enabled by item 136. Suction Pressure Optimisation When used in conjunction with JTL pack control and suction optimisers this unit is normally included in the suction pressure optimiser algorithm. It can be explicitly excluded by setting item 200 to 1. Daylight Saving When connected to a JTL network this controller can operate by displaying daylight saving time for its time and defrost schedule. Daylight saving operation is selected by setting item 18. The connected network controller then adjusts the times automatically during the daylight saving period. ADJUSTABLE PARAMETERS Range Units Cabinet temperature ratio Sensor selections Termination sensor selection Cabinet overtemperature tolerance Air off over temperature tolerance Alarm averaging time Cabinet temperature rate (second case) Cabinet overtemperature tolerance (second case) 20 to 80 0=off 1=on 0=off 1=on 0 to +20 0 to +30 00:30 to 03:00 20 - 100 0 - 120 hr:mn TEMPS & ALARMS 33 36-39 147 32 34 47 533 532 CONTROL 275 123 124 125 31 140 106 500 Control temperature Enable 2nd setpoint Primary cabinet temperature setpoint Secondary cabinet temperature setpoint Air off temperature setpoint Temperature control deadband Auxiliary output selection Enable second case 1=Air off 2=cabinet temp 0=disabled 1=enabled -30 to +10 -30 to +10 -39 to +5 0.4 to 3.0 0=off 1=Fan 2=Heater 0=Disabled 1=Enabled PULSED EXPANSION VALVE FUNCTIONS 157 158 161 188 189 162 186 163 187 164 170 171 174 175 177 179 273 Refrigerant type Pressure transducers zero offset Superheat measurement method Superheat control strategy Superheat setpoint Minimum superheat (pressure) Minimum superheat (2 temperature) Maximum valve opening (pressure) Minimum valve opening (2 temperature) Minimum valve opening PEV proportional gain PEV integral time constant High suction pressure shutdown Pressure transducer type Auto zero pressure enable Pressure display choice PEV override input 3 - 9 (R type shown on MU display) -7 to +7 1=2 temperature 2=pressure 0=SUCCEEDS, 1=SUCCEEDS with limit, 2=fixed 6.0 - 12.0 0 - 10 0-5 10 - 100 5 - 50 0 -50 1 - 100 1 - 250 0=disabled 1=enabled 3=-1 to 34 bar 4=-1 to 7 bar 0=disabled 1=auto 2=network 1=psi 2=bar 3=kPa 0=disable 1=enable 107 Defrost strategy 69 61 51-56 60 211 210 213 214 223 225 226 242 Number of defrosts expected or required Pump down time Defrost schedule Defrost schedule 12/24 hour clock Evaporator group Electrical supply distribution panel no Defrost heater circuit Defrost method Defrost requirement priority PREDICT Minimum time between defrosts PREDICT Maximum time between defrosts PREDICT override initiation 0=none 2=Network (learned backup)3=Time 5=PREDICT 7=Network (real time backup) 8=Coordinated (learned) 9=Coordinated (real time) 0 to 12 00:00 - 00:10 00:01 - 23:59 0=24hr 1=12hr 0=none 1=Lt 2=Ht 3=Satellite 1 to 15 panel no 1-15=circuit 0=brown phase 1=black phase 2=grey phase 3=3 phase 6=off cycle 1 to 8 2 to 8 6 to 72 0 - 100 DEFROST TERMINATION 144 50 145 57 59 49 Defrost termination method Defrost termination temp Minimum defrost time Defrost termination time Drain down time Refrigeration delay after defrost 1=Evaporator 2= Air off 3=Termination 4=Time only 0 to +20 00:00 - 00:30 00:05 to 00:59 00:00 to 00:10 00:00 to 00:10 FAN CONTROL 108 146 109 150 130 132 Fan control Temperature to turn fans off during defrost Fan delay after defrost Temperature to turn fans on after defrost Fan control sensor selection Fan control temperature setpoint 1=run always 2=off during defrost 3=fan controlled during defrost -12 to +20 00:00 - 00:10 -20 to +5 0=disabled 1=enabled -30 to +8 LIGHTING CONTROL 110 118 119 Jnet lighting control selection Lighting contractor selection Enable lights during shutdown 0=disabled 1=enabled 0=n.o 1=n.c 0=disabled 1=enabled Jnet FUNCTIONS 1 501 62 133 134 200 18 Unit number Unit number second case Jnet network shutdown selection Enable plant to override temp control Enable plant to cut off refrigeration Exclude from suction optimisation Daylight saving operation 0.1 - 899.8 0.1 - 899.8 0=disabled 1=enabled 0=off 1=on 0=disabled 1=enabled 0=include 1=exclude 0=standard time 1=daylight saving time 122 136 138 502 Temperature display choice Enable fans only mode from display Enable display controlled shutdown Enable 2nd display 0=Celsius 1=Fahrenheit 0=disabled 1=enabled O=Off 1=On 0=Disabled 1=Enabled DEFROST INITIATION Function DISPLAY LAPI item K K hr:mn K °C °C °C °C psi K K K % % % hr:mn hr:mn hours hours % °C hr:mn hr:mn hr:mn hr:mn °C hr:mn °C °C Bitswitch settings 21, o(CC) Frozen food (CO2), 1(CO) Frozen food (HFC), 2(OC) Chillers (HFC), 3(OO) Produce (HFC), where C = closed, O = open, closed = dot visible (0 to 3 is the virtual bitswitch setting on item 966) OTHER USEFUL ITEMS Item 20 21 22 23 24 520 521 131 141 30 28 240 241 Function TEMPERATURES Cabinet temperature Air on temperature Air off temperature Evaporator temperature Suction line temperature Cabinet temperature (second case) Air on temperature (second case) Energy saving temperature Termination sensor temperature CONTROL Cabinet temperature setpoint Effective air off setpoint Liquid valve open % Average liquid valve open % Item 154 155 156 159 166 168 169 181 182 190 Item PULSED EXPANSION VALVE FUNCTIONS Force pressure average to current reading Suction pressure Superheat Auto zero offset Force PEV opening (%) PEV valve opening (%) PEV status Time since last override (hr:mn) Duration of last override (sec) Modifier output (%) 70 274 72 74 111 112 113 114 115 Function MODE INPUTS & OUTPUTS Operating mode PEV override input state Defrost output state Auxiliary output state LIGHTING Communications lighting command Lighting override input state Lighting output state Force lights on Force lights off Item 40 41 42 46 77 78 79 261-272 219 221 222 243 63 203 Function DEFROST Duration of last defrost Time since end of last defrost Duration of this defrost Communications defrost command Forced defrost Inhibit defrost Forced refrigeration Learned defrost schedule Defrost arrangement from network Forced defrost requirement Enable forced defrost requirement PREDICT override average (%) Jnet NETWORK FUNCTIONS Network shutdown and fans only command states Associated plant suction lin