Display Controlled Fans Only Mode
The controller can be put into fans only mode using the display switch. This
feature is enabled by item 136.
Suction Pressure Optimisation
When used in conjunction with JTL pack control and suction optimisers this
unit is normally included in the suction pressure optimiser algorithm. It can be
explicitly excluded by setting item 200 to 1.
Daylight Saving
When connected to a JTL network this controller can operate by displaying
daylight saving time for its time and defrost schedule. Daylight saving operation
is selected by setting item 18. The connected network controller then adjusts
the times automatically during the daylight saving period.
ADJUSTABLE PARAMETERS
Range
Units
Cabinet temperature ratio
Sensor selections
Termination sensor selection
Cabinet overtemperature tolerance
Air off over temperature tolerance
Alarm averaging time
Cabinet temperature rate (second case)
Cabinet overtemperature tolerance (second case)
20 to 80
0=off 1=on
0=off 1=on
0 to +20
0 to +30
00:30 to 03:00
20 - 100
0 - 120
hr:mn
TEMPS & ALARMS
33
36-39
147
32
34
47
533
532
CONTROL
275
123
124
125
31
140
106
500
Control temperature
Enable 2nd setpoint
Primary cabinet temperature setpoint
Secondary cabinet temperature setpoint
Air off temperature setpoint
Temperature control deadband
Auxiliary output selection
Enable second case
1=Air off 2=cabinet temp
0=disabled 1=enabled
-30 to +10
-30 to +10
-39 to +5
0.4 to 3.0
0=off 1=Fan 2=Heater
0=Disabled 1=Enabled
PULSED EXPANSION VALVE
FUNCTIONS
157
158
161
188
189
162
186
163
187
164
170
171
174
175
177
179
273
Refrigerant type
Pressure transducers zero offset
Superheat measurement method
Superheat control strategy
Superheat setpoint
Minimum superheat (pressure)
Minimum superheat (2 temperature)
Maximum valve opening (pressure)
Minimum valve opening (2 temperature)
Minimum valve opening
PEV proportional gain
PEV integral time constant
High suction pressure shutdown
Pressure transducer type
Auto zero pressure enable
Pressure display choice
PEV override input
3 - 9 (R type shown on MU display)
-7 to +7
1=2 temperature 2=pressure
0=SUCCEEDS, 1=SUCCEEDS with limit, 2=fixed
6.0 - 12.0
0 - 10
0-5
10 - 100
5 - 50
0 -50
1 - 100
1 - 250
0=disabled 1=enabled
3=-1 to 34 bar 4=-1 to 7 bar
0=disabled 1=auto 2=network
1=psi 2=bar 3=kPa
0=disable 1=enable
107
Defrost strategy
69
61
51-56
60
211
210
213
214
223
225
226
242
Number of defrosts expected or required
Pump down time
Defrost schedule
Defrost schedule 12/24 hour clock
Evaporator group
Electrical supply distribution panel no
Defrost heater circuit
Defrost method
Defrost requirement priority
PREDICT Minimum time between defrosts
PREDICT Maximum time between defrosts
PREDICT override initiation
0=none 2=Network (learned backup)3=Time 5=PREDICT
7=Network (real time backup) 8=Coordinated (learned) 9=Coordinated (real time)
0 to 12
00:00 - 00:10
00:01 - 23:59
0=24hr 1=12hr
0=none 1=Lt 2=Ht 3=Satellite
1 to 15 panel no
1-15=circuit
0=brown phase 1=black phase 2=grey phase 3=3 phase 6=off cycle
1 to 8
2 to 8
6 to 72
0 - 100
DEFROST
TERMINATION
144
50
145
57
59
49
Defrost termination method
Defrost termination temp
Minimum defrost time
Defrost termination time
Drain down time
Refrigeration delay after defrost
1=Evaporator 2= Air off 3=Termination 4=Time only
0 to +20
00:00 - 00:30
00:05 to 00:59
00:00 to 00:10
00:00 to 00:10
FAN CONTROL
108
146
109
150
130
132
Fan control
Temperature to turn fans off during defrost
Fan delay after defrost
Temperature to turn fans on after defrost
Fan control sensor selection
Fan control temperature setpoint
1=run always 2=off during defrost 3=fan controlled during defrost
-12 to +20
00:00 - 00:10
-20 to +5
0=disabled 1=enabled
-30 to +8
LIGHTING
CONTROL
110
118
119
Jnet lighting control selection
Lighting contractor selection
Enable lights during shutdown
0=disabled 1=enabled
0=n.o 1=n.c
0=disabled 1=enabled
Jnet FUNCTIONS
1
501
62
133
134
200
18
Unit number
Unit number second case
Jnet network shutdown selection
Enable plant to override temp control
Enable plant to cut off refrigeration
Exclude from suction optimisation
Daylight saving operation
0.1 - 899.8
0.1 - 899.8
0=disabled 1=enabled
0=off 1=on
0=disabled 1=enabled
0=include 1=exclude
0=standard time 1=daylight saving time
122
136
138
502
Temperature display choice
Enable fans only mode from display
Enable display controlled shutdown
Enable 2nd display
0=Celsius 1=Fahrenheit
0=disabled 1=enabled
O=Off 1=On
0=Disabled 1=Enabled
DEFROST INITIATION
Function
DISPLAY
LAPI
item
K
K
hr:mn
K
°C
°C
°C
°C
psi
K
K
K
%
%
%
hr:mn
hr:mn
hours
hours
%
°C
hr:mn
hr:mn
hr:mn
hr:mn
°C
hr:mn
°C
°C
Bitswitch settings 21, o(CC) Frozen food (CO2), 1(CO) Frozen food (HFC), 2(OC) Chillers (HFC), 3(OO) Produce (HFC), where C = closed, O = open, closed = dot visible (0 to 3 is the virtual bitswitch setting on item 966)
OTHER USEFUL ITEMS
Item
20
21
22
23
24
520
521
131
141
30
28
240
241
Function
TEMPERATURES
Cabinet temperature
Air on temperature
Air off temperature
Evaporator temperature
Suction line temperature
Cabinet temperature (second case)
Air on temperature (second case)
Energy saving temperature
Termination sensor temperature
CONTROL
Cabinet temperature setpoint
Effective air off setpoint
Liquid valve open %
Average liquid valve open %
Item
154
155
156
159
166
168
169
181
182
190
Item
PULSED EXPANSION VALVE FUNCTIONS
Force pressure average to current reading
Suction pressure
Superheat
Auto zero offset
Force PEV opening (%)
PEV valve opening (%)
PEV status
Time since last override (hr:mn)
Duration of last override (sec)
Modifier output (%)
70
274
72
74
111
112
113
114
115
Function
MODE INPUTS & OUTPUTS
Operating mode
PEV override input state
Defrost output state
Auxiliary output state
LIGHTING
Communications lighting
command
Lighting override input state
Lighting output state
Force lights on
Force lights off
Item
40
41
42
46
77
78
79
261-272
219
221
222
243
63
203
Function
DEFROST
Duration of last defrost
Time since end of last defrost
Duration of this defrost
Communications defrost command
Forced defrost
Inhibit defrost
Forced refrigeration
Learned defrost schedule
Defrost arrangement from network
Forced defrost requirement
Enable forced defrost requirement
PREDICT override average (%)
Jnet NETWORK FUNCTIONS
Network shutdown and fans only command
states
Associated plant suction lin