User Guide Revision 1.12
IP55 Quick Start Up Guide
Mechanical Mounting
Information can be found in section 3.6.
HVAC Display
(Status, Diagnostics, and Programming)
Keypad Operation can be found in
section 5.5
Hardware Enable
Link the terminals as shown, optionally
through switch contacts to enable drive
operation
Supply Voltage
Control Terminal
Configuration based on factory settings
RJ45
Connector
Run / Stop
10K Pot
Close the switch to run (enable)
Open the switch to stop
Fuses or MCB
Check Drive
Rating info in
section 13.4
PE
L1 L2 L3
AC Supply Connection
200 – 240 Volts + / - 10%
380 – 380 Volts + / - 10%
Check Drive Input Voltage
information in section 13.2
Motor Cable
For correct cable size, see Technical
Data in section 13.4.
Observe the maximum permissible
motor cable length.
For Motor cable lengths > 50 metres, an
output filter is recommended.
Use a screened (shielded cable). The
shield should be bonded to earth at
both ends.
Motor Connection
Check for Star or Delta connection
according to the motor voltage rating in
section 4.5.
Motor Nameplate Details
Motor Rated Voltage: P1-07
Motor Rated Current: P1-08
Motor Rated Frequency: P1-09
Motor Rated Speed (Optional): P1-10
2