SETTINGS
203GT has three types of settings:
a) user level settings which the user can adjust (p. 6-8)
b) maintenance mode settings which the maintenance person may have
to adjust
c) special maintenance mode settings which seldom have to be adjusted
(p. 30)
Directions for entering the
maintenance mode are on page 19.
H1 Maint mode
Tuning values
Settings
Trends
The original factory settings are restored in special maintenance (p. 29)
Press the
H1 Settings
OutdoorDelay 2h
Pre-increase 0h
button to move the cursor to "Settings". Press OK.
Press the
button to move the cursor to the setting whose value you
want to change. Press OK.
Press the - or + button to change the setting. Press OK.
Press the
HW Settings
HW alarm
70°C
button to move to the HW regulating circuit
Press the
button to move the cursor to the setting whose value you
want to change. Press OK.
Press the - or + button to change the setting. Press OK.
INFORMATION ABOUT MAINTENANCE MODE SETTINGS:
Settings:
Factory
settings:
Range:
Outdoor
temperature
delay
H1: 2 h
H2: 0 h
0...20h
0...20h
Pre-increase
H1: 0 h
H2: 0 h
0...5h
0...5h
70 °C
65...120°C
HW alarm
Explanation:
Attention!
The length of the outdoor temperature
measurement follow-up period from
which the regulator calculates the
average. Supply water regulation and
pump control occur on the basis of the
measurement of the average.
The duration of the automatic preincrease after the reduced operation
mode.
Domestic hot water alarm limit.
The alarm limit automatically
rises during an increase in
HW.
21