Download SERVICE MANUAL
Transcript
10-1-3. Optional Connector Specifications of Indoor P.C. Board Function Humidifier output Fan output — Option output Outside error input Connector No. Pin No. CN66 DC12V Output DC12V Output ON/OFF input 0V (COM) Operation output CN32 CN61 CN60 CN80 Remarks Specifications In heating, thermo ON, Fan ON, Humidifier output ON * Humidifier provided, Drain pump ON is set up by CN70 short-circuit or from remote controller. (DN=40) Shipment setup: ON with indoor unit operation and OFF with stop are linked. * Single operation by FAN button on remote controller is set up from remote controller (DN=31) HA ON/OFF input (J01: YES/NO=Pulse (At shipment) / Static input select) Main prohibition input Operation stop of main remote controller is permitted / prohibited by input. ON during operation (Answerback of HA) DC12V (COM) Alarm output ON during alarm output DC12V (COM) Defrost output ON when outdoor unit is defrosted Thermo ON output ON during Real thermostat ON (Compressor ON) COOL output ON when operation mode is cooling system (COOL, DRY, Cool/Heat Auto cooling) HEAT output ON when operation mode is heating system (HEAT, Cool/Heat Auto cooling) Fan output ON when indoor fan is ON (During use of air cleaner/Interlock cabling) DC12V (COM) Generate check code “L30” (for 1 minute continuously) to stop forcedly the operation. DC12V (COM) Outside error input — CN20 — — — — CN70 — — — CHK operation check CN71 Check mode input 0V Display mode input 0V Exhibition mode enables to communicate by indoor unit and remote controller only. (When power has been turned on.) Timer short (Usual) Demand input Indoor unit forced thermostat OFF operation DISP exhibition mode EXCT demand CN72 CN73 0V 223 Used for indoor operation check. (Outdoor does not communicate with remote controller, and outputs specified operation such as indoor fan “H”, drain pump ON, etc.)