9.2 Overview of Function Codes
F23
Starting Frequency
F25
Stop Frequency
At the startup of an inverter, the initial output frequency is equal to the starting frequency.
The inverter stops its output at the stop frequency.
Set the starting frequency to a level that will enable the motor to generate enough torque for
startup. Generally, set the motor's rated slip frequency at the starting frequency F23.㩷
- Data setting range: 0.0 to 60.0 (Hz) (for both starting and stop frequencies)
If the starting frequency is lower than the stop frequency, the inverter will not
output any power as long as the frequency command does not exceed the stop
frequency.
F27
Motor Sound (Tone)
Refer to H98.
„ Motor sound (Carrier frequency) (F26)
F26 controls the carrier frequency so as to reduce an audible noise generated by the motor or
inverter itself, and to decrease a leakage current from the main output (secondary) wirings.
Carrier frequency
Inverter rated capacity: 0.75 to 22 kW
0.75 to 15 kHz
Inverter rated capacity: 30 to 75 kW
0.75 to 10 kHz
Inverter rated capacity: 90 to 500 kW
0.75 to 6 kHz
Motor sound noise emission
High l Low
Motor temperature (due to harmonics components)
High l Low
Ripples in output current waveform
Large l Small
Leakage current
High l Low
Electromagnetic noise emission
High l Low
Inverter loss
High l Low
9-45
FUNCTION CODES
Motor Sound (Carrier frequency)
Chap. 9
F26