Download Operating Instructions - Cont

Transcript
Electrical Installation
Signal terminals overview
Signal terminals overview
0V
Relay common
AO/DO
9 10 11
0V
0V
8
AI/DI
AO/DO
7
+10 V
0V
6
DI 3
AI/DI
5
DI 2
+10 V
4
1
2
3
4
5
6
7
8
9 10 11
REV
DI 3
3
DI 1
DI 2
2
+24 V
DI 1
1
FWD
+24 V
Relay common
IP55 with switch option
Relay contact
IP20 and IP55
Relay contact
5.3
5
64485AEN
64608AEN
The signal terminal block has the following signal connections:
Terminal
no.
Signal
Connection
Description
1
+24 V ref out
+24 V ref out
Ref. to activate DI1 ... DI3 (100 mA max.)
2
DI 1
Digital input 1
3
DI 2
Digital input 2
4
DI 3
Digital input 3 /
thermistor contact
Positive logic
"Logic 1" inout voltage range: DC 8... 30 V
"Logic 0" inout voltage range: DC 0... 2 V
Compatible with PLC requirement when 0 V is
connected.
5
+10 V
+10 V ref out
10 V ref for analog input
(pot supply +, 10 mA max., 1 K Ω min.)
6
AI / DI
Analog input (12 bit)
Digital input 4
0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA
"Logic 1" input voltage range: DC 8 ... 30 V
7
0V
0 V common
0 V ref for analog input (pot supply –)
8
AO / DO
Analog output (10 bit)
Digital output
0 ... 10 V, 20 mA analog
24 V, 20 mA digital
9
0V
0 V common
0 V ref for analog output
10
Relay contact
Relay contact
N.O. relay contact (AC 250 V / DC 30 V @ 5 A)
11
Relay common
Relay common
All digital inputs activated by input voltage in range +8 V ... 30 V, i.e. +24 V compatible.
STOP!
Voltages greater than 30 V applied to the control terminals may result in damage to the
controller.
Only apply voltages up to 30 V to the control terminals.
Operating Instructions – MOVITRAC® LTE-B
21