Download Operating Instructions - Cont
Transcript
Electrical Installation Signal terminals overview Signal terminals overview 0V Relay common AO/DO 9 10 11 0V 0V 8 AI/DI AO/DO 7 +10 V 0V 6 DI 3 AI/DI 5 DI 2 +10 V 4 1 2 3 4 5 6 7 8 9 10 11 REV DI 3 3 DI 1 DI 2 2 +24 V DI 1 1 FWD +24 V Relay common IP55 with switch option Relay contact IP20 and IP55 Relay contact 5.3 5 64485AEN 64608AEN The signal terminal block has the following signal connections: Terminal no. Signal Connection Description 1 +24 V ref out +24 V ref out Ref. to activate DI1 ... DI3 (100 mA max.) 2 DI 1 Digital input 1 3 DI 2 Digital input 2 4 DI 3 Digital input 3 / thermistor contact Positive logic "Logic 1" inout voltage range: DC 8... 30 V "Logic 0" inout voltage range: DC 0... 2 V Compatible with PLC requirement when 0 V is connected. 5 +10 V +10 V ref out 10 V ref for analog input (pot supply +, 10 mA max., 1 K Ω min.) 6 AI / DI Analog input (12 bit) Digital input 4 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA "Logic 1" input voltage range: DC 8 ... 30 V 7 0V 0 V common 0 V ref for analog input (pot supply –) 8 AO / DO Analog output (10 bit) Digital output 0 ... 10 V, 20 mA analog 24 V, 20 mA digital 9 0V 0 V common 0 V ref for analog output 10 Relay contact Relay contact N.O. relay contact (AC 250 V / DC 30 V @ 5 A) 11 Relay common Relay common All digital inputs activated by input voltage in range +8 V ... 30 V, i.e. +24 V compatible. STOP! Voltages greater than 30 V applied to the control terminals may result in damage to the controller. Only apply voltages up to 30 V to the control terminals. Operating Instructions – MOVITRAC® LTE-B 21