VOLTAGE INPUT
Range
Accuracy
Thermal drift
Input impedance
Linearisation
*Slidewire
± 100 mV, ± 1 V, ± 5 V, ± 10 V, (1 to 5) V
0.04 % FS ± 0.04 % of reading
0.02 %/°C
1 MΩ
Linear, Square root, Power 3/2, Power 5/2, Custom
3 wire Potentiometer inputs can be accommodated between 50 Ω and 10 KΩ
RELAY OUTPUTS
Two relay options are available, either a single changeover or twin independent relays with normally closed
contacts.*¹
Alarm Action
Hysteresis
Delay Time*²
Start-up Delay
Off, High, Low, Deviation, Test
Programmable (0 to 100) %
Programmable
Programmable
Max. Switching Voltage
Max. Current
Max. Power
Contact Resistance
Operate Time
Electrical Life @ Full Load
Mechanical Life
AC
DC
48 V RMS
48 V
1 A @ 48 V
1 A @ 30 V
60 VA
30 W
< 100 mΩ
< 5 ms
100 000 operations
10 000 000 operations
3.1.2 FREQUENCY INPUTS 23XX AND 24XX ONLY
A wide range of input types and frequencies can be accommodated without the need for Switches or
Jumpers. Totalise functions are a standard feature on the single channel version and are stored during
power down.
Input Types
Frequency range
Accuracy
Namur, Low Voltage (> 10 mV), TTL, Open Collector, PFC
0.1 Hz to 20 kHz.
0.003% FS
DIGITAL INPUTS 21XX AND 23XX ONLY
Single channel units can also accept two external digital inputs which can be TTL, Open Collector, 24 VDC
Logic or Potential Free Contacts. Dig 1 is dedicated to a reset/clear function enabled by the configuration
software whilst Dig 2 is reserved for use with TFML. Both digitals can be read via the communications and
used to signal events.
OUTPUTS
Two output option types are available per channel, relay or current re-transmission. The configuration of
these will vary depending upon whether they are fitted on the single or dual channel transmitter.
CURRENT RE-TRANSMISSION
Output Range
Single Channel
Dual Channel
Max. Current Output
Accuracy
Max Power Supply
Temperature Stability
OUTPUTS
(0 to 10) mA, (0 to 20) mA, (4 to 20) mA source or sink
(4 to 20) mA sink
< 23 mA
0.07 % or 5 mA, whichever is greater
30 V (In SINK mode)
5 µA/°C
*NOTE: Maximum source load 750 R
*NOTES:
1. Contacts are normally closed i.e the contact is closed at power off and when operating in an alarm
condition. The contact opens in the absence of an alarm condition. The active function can be reversed
in software.
2. Alarm must be continuously present for this period in order to be recognised
3.2 GENERAL
Response Time
Filter
Power Requirements
Breakdown Isolation
Ambient Operating Range
Ambient Storage
Ambient Humidity
EMC Emissions
EMC Immunity
Display Range
300 ms
Programmable or Adaptive
24 VDC ± 10 % @ 200 mA
1 kV I/P~O/P~PSU
(-30 to 60) °C
(-50 to 85) °C
(10 to 90) % RH
BS EN61326
BS EN61326
-1999 to 9999
4.0 INSTALLATION
THIS SECTION FOR USE BY COMPETENT PERSONNEL ONLY
SAFETY INFORMATION
WARNING!
THE EQUIPMENT MUST BE INSTALLED BY SUITABLY QUALIFIED PERSONNEL AND
MOUNTED IN AN ENCLOSURE PROVIDING PROTECTION TO AT LEAST IP20. THE
EQUIPMENT CONTAINS NO USER SERVICEABLE PARTS.
4.1 ISOLATION
The 24 VDC power supply and RS485 comms bus share the same common connections. Isolation is provided
between input, output and supply/comms breakdown isolation voltage 500 VAC RMS flash tested to 1 kVDC.
Page 3