11. APPENDIX 2: ADVANCED FUNCTIONS
11.1 Skip defrost
Possible operating sequence (for example, if d12 = 2):
This algorithm is used to determine whether the shorter duration of a
defrost allows subsequent defrosts to be skipped. To enable the function,
set d12 = 2 or 3.
Start count
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
…
Par. Description
d12 Advanced defrosts
d12
0
1
2
3
dn
dH
dP1
dP2
Skip defrost
Disabled
Disabled
Enabled
Enabled
Def Min Max UOM
0
0
3
Automatic variation of dI
Disabled
Enabled
Disabled
Enabled
Nominal defrost duration
Proportional factor for variation of dI
Maximum defrost duration
Maximum aux evaporator defrost duration
65
50
30
30
1
0
1
1
100
100
250
250
%
min/s
min/s
Tab. 11.a
The nominal defrost times on evaporator 1 and evaporator 2 (auxiliary
evaporator) are determined based on parameter dn and the parameters
that set the maximum defrost duration for evaporators 1 and 2, according
to the following formulae:
dn1 =
dn2 =
dn
100
dn
100
dP1
dP2
Skip count
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
1
1
2
2
2
0
0
0
0
1
1
2
2
2
Current count
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
0
2
1
0
0
0
0
0
1
0
2
1
0
Defrost
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Performed
Skipped
Defrost
Performed
Performed
Performed
Skipped
Defrost
Skipped
Skipped
Defrost
Performed
Performed
Performed
Performed
Skipped
Defrost
Skipped
Skipped
Defrost
Outcome
Not tested
Not tested
Not tested
Not tested
Not tested
Not tested
Not tested
> “dn”
> “dn”
> “dn”
> “dn”
< “dn”
> “dn”
> “dn”
> “dn”
< “dn”
< “dn”
> “dn”
> “dn”
> “dn”
> “dn”
< “dn”
< “dn”
< “dn”
Tab. 11.b
The algorithm keeps a counter of the defrosts to be skipped:
• if the defrost ends after a time less than dn1, the counter of defrosts to
be skipped is increased by 1;
• if the defrost ends normally, the next defrost is performed;
• when the counter reaches a total of 3, 3 defrosts are skipped and then
the counter returns to 1;
• when powering on the controller, 7 defrosts are completed without
increasing the value, after which the counter is enabled (starting from
the eighth defrost).
11.2 Variation of the defrost interval
This algorithm is used to adjust the defrost interval based on the duration
of the previous defrost. To enable this, set d12 = 1 or 3.
The nominal defrost times on evaporator 1 and evaporator 2 are
determined based on parameter dn and the parameters that set the
maximum defrost duration for evaporators 1 and 2, according to the
following formulae:
Note: if there are two evaporators, the defrost duration used to
determine the defrosts to be skipped is the longer nominal defrost
duration.
dn1 =
dn2 =
dn
100
dn
100
dP1
dP2
With running the defrost, depending on the duration “dE”, the defrost
interval “dI” is adjusted by the value “ΔdI”, calculated using the algorithm.
If there are two evaporators, the defrost duration considered is the longer
nominal defrost duration.
ir33plus +03Z0028EN rel. 1.0 - 27.08.2014
44