Download User's Manual
Transcript
The outside power supply used for Digital Input is from 16Vdc to 30Vdc. If the switch is far from EV/DV Series the meter, the voltage of power supply could be higher. The maximum current in the circuit should not over 10mA. The wire number of Digital input could be AWG16~22 or 0.6~1.5mm2. Relay Output There are two additional relay output for option in the meter. The terminal are R11, R12 (16, 17) and R21, R22 (18, 19). These two relay output are used to remote control 16 EV190 R11 Power Supply Mediate Relay + R12 Control Output 17 electric switch in power system. Relay type is mechanical Form A contact with 3A/250V Fig 2.12 Relay Output or 3A/30Vdc. A mediate relay is recommended in the output circuit as in Fig 2.12. There are two relay output modes for selection, one is latching, and the other is momentary. For the latching mode, the relay can be used to output two statues on or off. For the momentary mode, the output of the relay changes from off to on for a period of time Ton and than goes off. Ton can be setting from 50- 3000ms. The wire of relay output should be chose between AWG22 (0.5mm2)~AWG16 (1.5mm2). 16