Download User`s Manual - AMETEK Power Instruments
Transcript
POWER INSTRUMENTS Addr Fun Data start reg hi 11H 01H 00H Data start reg lo Data #of regs hi Data #of regs lo CRC16 Hi CRC16 Lo 00H 00H 02H BFH 5BH Table 4.4 Relay status query message Response The meter response includes the meter address, function code, quantity of data byte, the data, and error checking. An example response to read the status of Relay1 and Relay2 is shown in Table 4.5. The status of Relay1 and Relay2 is responding to the last 2 bits of the data. Relay1: bit0 Relay2: bit1. The content of the data is, Addr 11H Fun 01H Byte count Data 01H 02H CRC16 Hi CRC16 Lo D4H 89H Table 4.5 Relay status responds 7 6 5 4 3 2 1 0 0 0 0 0 0 0 1 0 LSB MSB (Relay 1 = OFF , Relay 2=ON) 2. Read the Status of DI Function Code 02 Query 1=On 0=Off 41