Download Eclipse RS485 Communication Protocol

Transcript
HARDWARE REQUIREMENTS
Modem
Cable
PC
UNIT # 3
Com
Converter
RS-485
Cable
RS-232
to
RS-485
UNIT # 2
UNIT # 4
UNIT # 1
UNIT # X
Modem cable – generally, a 9 pin M to a 9 pin F, straight-through cable, depending upon
the PC’s com port, and the communication converter’s RS-232 port.
Com converter – converts full duplex RS-232 to half duplex RS-485. Durant part number
58801-460, or 58801-461, or equivalent.
RS-485 cable – 3 conductor, shielded cable, Belden 9925 or equivalent. Maximum
distance from com converter to Unit #X is 4000 ft. A second com converter may be
added as a repeater if the network length exceeds 4000 ft.
Units – Durant Ambassador and / or Eclipse series. Each unit is assigned a unique
address in the range of 0-99 decimal. Addresses do not have to correspond to the unit’s
location on the network.
3
CHS Controls AB
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se www.chscontrols.se