Download Corrigo E - User Manual - Xref controls e-shop
Transcript
External setpoint Not active Min setp.: 12.0 °C Max setp.: 30.0 °C For details, see section 5.1.9 External setpoint. 9.15 Run indication / Motor protection Digital input signals are used to supervise fans and pumps. They can be configured either for indication of the motor running or for monitoring of motor protection contacts. An input configured for run indication should normally be closed. Open input when the motor is running, i.e. motor control output is activated, will generate an alarm. For supply air fans and exhaust air fans, there is also a conflict alarm, i. e. an alarm if the run indication input is closed even though the motor control output is not activated. See alarm 33 External activ. SAF and alarm 34 External activ. EAF in section 9.19 Alarm configuration. An input configured as motor protection should be normally open, i. e. closed contact when the motor is running, i.e. motor control output is activated, will generate an alarm. Run ind./Motor prot SAF: Run ind EAF: Run ind Run ind./Motor prot P1 Heat: Run ind P1 Cool: Run ind P1 Exch: Run ind When running frequency controlled fans, the pressure signal from each respective fan’s pressure transmitter is normally used as run indication signal. If the pressure falls below the set value during normal operation, a malfunction alarm is activated. Min pressure for run indication SAF: 25.0 Pa EAF: 25.0 Pa Alarm from frequency converter When running frequency controlled fans, you sometimes want to use both a pressure signal from a pressure transmitter and a digital alarm signal from a frequency converter. An analogue input for a pressure transmitter and a digital input for SAF or EAF indication must then be configured. The setting Run indication/Motor protection SAF or EAF must be set to Motor protection. A fan alarm will be activated both when there is no pressure signal from the pressure transmitter, and when the digital signal Indication SAF or EAF is activated. 9.16 Actuator type Choose output signals to the actuators connected to the analogue control outputs: 0…10 V DC, 2…10 V DC, 10…0 V DC or 10…2 V DC. Actuator type Y1 Heating: 0-10V Y2 Exchan.: 0-10V Y3 Cooling: 0-10V Corrigo E Ventilation manual, revision G Chapter 9 Configuration 47