Download Corrigo E - User Manual - Xref controls e-shop

Transcript
External setpoint
Not active
Min setp.: 12.0 °C
Max setp.: 30.0 °C
For details, see section 5.1.9 External setpoint.
9.15 Run indication / Motor protection
Digital input signals are used to supervise fans and pumps. They can be configured either for
indication of the motor running or for monitoring of motor protection contacts.
An input configured for run indication should normally be closed.
Open input when the motor is running, i.e. motor
control output is activated, will generate an alarm.
For supply air fans and exhaust air fans, there is also a conflict alarm, i. e. an alarm if the run
indication input is closed even though the motor control output is not activated. See alarm 33
External activ. SAF and alarm 34 External activ. EAF in section 9.19 Alarm configuration.
An input configured as motor protection should be normally open, i. e. closed contact when the
motor is running, i.e. motor control output is activated, will generate an alarm.
Run ind./Motor prot
SAF: Run ind
EAF: Run ind
Run ind./Motor prot
P1 Heat: Run ind
P1 Cool: Run ind
P1 Exch: Run ind
When running frequency controlled fans, the pressure signal from each respective fan’s pressure
transmitter is normally used as run indication signal. If the pressure falls below the set value during
normal operation, a malfunction alarm is activated.
Min pressure for
run indication
SAF: 25.0 Pa
EAF: 25.0 Pa
Alarm from frequency converter
When running frequency controlled fans, you sometimes want to use both a pressure signal from a
pressure transmitter and a digital alarm signal from a frequency converter. An analogue input for a
pressure transmitter and a digital input for SAF or EAF indication must then be configured. The
setting Run indication/Motor protection SAF or EAF must be set to Motor protection. A fan alarm
will be activated both when there is no pressure signal from the pressure transmitter, and when the
digital signal Indication SAF or EAF is activated.
9.16 Actuator type
Choose output signals to the actuators connected to the analogue control outputs: 0…10 V DC,
2…10 V DC, 10…0 V DC or 10…2 V DC.
Actuator type
Y1 Heating: 0-10V
Y2 Exchan.: 0-10V
Y3 Cooling: 0-10V
Corrigo E Ventilation manual, revision G
Chapter 9 Configuration
47