8.1.5 Digital outputs Digital output 1 Signal: HS1-PumpA Auto Status: On 8.2 HS Heating System, supply 8.2.1 Parallel displacement To each of the set control curves can be added a parallel displacement. Parallel displacemnt HS1: 0.0 °C HS2: 0.0 °C HS3: 0.0 °C 8.2.2 Maximum limit A maximum supply temperature can be set individually for each heating system. Maximum limit HS1: 98 °C HS2: 98 °C HS3: 98 °C 8.2.3 Minimum limit A minimum supply temperature can be set individually for each heating system. Minimum limit HS1: 0 °C HS2: 0 °C HS3: 0 °C 8.2.4 Auto-correction of setpoint Room sensors can be used to correct the control curves. The average room temperature error over 24 hours is calculated. Values 1 hour before and 1 hour after a day/night or night/day change-over are ignored. The curves are corrected once daily using the average room temperature error and a settable correction factor. The correction will be a parallel displacement of the entire curve using the following formula: Displacement = (Room setpoint - Average temp)*Factor Auto-correction Setpoint HS1 On Æ Corr. factor HS1 2.0 Present correction 0.6°C Corrigo E Heating manual, revision G Chapter 8 Configuration 28