Download ECARS Operating Instructions
Transcript
Select Output Equipment Control. Selecting Output Equipment Control will give you a screen that shows all of the device programs for that room. The output state for the Panel Control should read Manual On. If it doesn’t, left click on the Manual Off or Auto Off and change it to Manual On. If none of the above methods restores the alarm to normal function then the problem is within the communications between the networked panels. Communications loss To check the status of the panel: Select Factory Screens from the home page. Select the controller of choice e.g. C10 #151 1-4. Select Installation & Service Settings. Select Device Network Communications. The screen that will come up will indicate the devices on the network. The unit that has failed will display not communicating in the status column and the timer will read 255. There are a limited number of situations that can occur: • There is a problem with the wire between panels • The panel that is in alarm has failed • The panel before it in the network has failed Page 21 of 22