Tab. 19: Measuring distance
Model name
Depth of field
Depth of field at reduced accuracy
OLV40
120 mm ± 5 mm
120 mm ± 20 mm
OLV80
240 mm ± 10 mm
240 mm ± 40 mm
Fig. 6: Assembly tolerance for
the OLV
Direction of movement
Direction of movement
14.3
14.3.1

WARNING
Electrical connection
Wiring notes
Use screened cables for supply and interfaces.
A correct and complete cable shielding concept is required for trouble-free operation.
Special care must be taken to ensure cable shield contact with the control cabinet and
the OLV.
The cable shield of the pre-wired M12 cable is connected to the metal male connector
and thus also to the housing of the OLV. The cable shield at the control cabinet must be
connected to the operating ground over a large surface area. Appropriate measures must
be taken to prevent equipotential bonding currents flowing through the cable shield.
Reliable data transmission is only possible when using screened cables with twisted-pair
conductors.
14.3.2
Connection of the OLV
1. Connect the supplied sensor cable to the OLV via the M12 male connector on the
sensor head.
2. Connect the other end (SUB-D male connector) of the sensor cable (part number 6048589)
with a separately purchased SBX-OLV connection box (part number 6048590). Refer to the
respective instructions for the SBX-OLV for information about its connection options.
3. Alternative for point 2: Connect the open end of the sensor cable according to
the designated functions.
4. Connect the emergency switching off input (see Chapter 15.2.2, Page 46) with a keyoperated pushbutton (the key for which may only be removed in the laser-off state)
and, if required, with one or more additional emergency switching off devices
(in series).