08.2009 8.9 Parameterization Motor identification From Version V1.30 onwards, automatic motor identification is available. In the case of Siemens motors (P095 = 1 or 2 ) the motor type is first selected in P096 or P097. In the case of non-Siemens motors (P095 = 3 or 4), the rating plate data and number of pole pairs have to be entered, and then automatic paramterizing is called with P115 = 1. After exit from the "drive initial start-up" status with P060 = 1, P115 = 2 is set and hence motor identification is selected. The converter must now be switched in within 30 s so that measuring can start. The alarm A078 is set during the 30 s. CAUTION The motor shaft can move slightly during the measurement operation. The motor cables are live. Voltages are present at the converter output terminals and hence also at the motor terminals; they are therefore hazardous to touch. WARNING It must be ensured that no danger for persons and equipment can occur by energizing the power and the unit. If measurement is not started within 30 s or if it is interrupted by an OFF command, error F114 is set. The converter status during measurement is "Motid-Still" (r001 = 18). Measurement is ended automatically, and the converter reverts to the status "Ready for start-up” (r001 = 009). In current-controlled mode (P290 = 0), automatic motor indentification should always be performed during initial start-up. 8.10 Complete parameterization To make full use of the complete functionality of the inverter/converter, parameterization must be carried out in accordance with the "Compendium". You will find the relevant instructions, function diagrams and complete lists of parameters, binectors and connectors in the Compendium. Language Compendium order number German 6SE7080-0QX70 English 6SE7087-6QX70 French 6SE7087-7QX70 Spanish 6SE7087-8QX70 Italian 6SE7087-2QX70 Siemens AG 6SE7087-8KP50 SIMOVERT MASTERDRIVES Operating Instructions 8-49